Flameproof Junction Box

By: Prompt Engineering Works

CategoryIndustrial Components and PartsManufacturerPrompt Engineering WorksMin Order Quantity1.00 UnitDelivery Lead TimeAs per orderPlace of OriginIndiaSupply AbilityCustomization as requiredPackaging DetailsStandard export packingTransportation DetailsRoad / Ship
*Login Required

Details

Price:Available on request

Description

  • Type of Protection: Flameproof (explosion proof) Ex-d or increased safety Ex-e
  • Area Classification: Zone 1 and 2 or zone 2
  • Gas Groups: I, IIA, IIB and IIC
  • IP Protection: Minimum IP 55 or IP 65/66
  • Apparatus Standard: For Ex-d – IS 2148/1981 and Ex-e IS 6381/1972 and IS 8224/1976
  • Material: Cast aluminium alloy LM-6
  • Finish: Corrosion-resistant epoxy paint shade 631 of IS 5
  • Gasket: Endless neoprene minimum 3 mm dia
  • Hardware: All flame path–SS allen bolt or threaded. All other SS
  • Mounting: Wall/structure mounting arrangement using bolt of minimum M8
  • Rating: As per customer specification various type of terminals like clip-on strip type, busbar, Ex-i or Ex-e terminals of minimum 2.5 Sq. mm, 230V, 50 Hz AC
  • Cable Entry Size/No: As per customer specification. Size and type like NPT, BSP, BSCon, Metric PG on the LEFT/RIGHT/BOTTOM and top side of junction box
  • Earthing: External 2 Nos. of size M6 and internal 1 No. of size M6
  • Accessories: (OPTIONAL) cable gland and stopping plug, mounting hardware